| Andrew Edge |
Posted: Tue Feb 13, 2007 12:51 pm |
|
|
|
Guest
|
Hi.
Can anyone help me to know
what the typical Electric Power consumption is for a gas boiler having
a maximum heat output of 120000KCal/h.
Andy |
|
|
| Back to top |
|
| john jardine |
Posted: Tue Feb 13, 2007 4:35 pm |
|
|
|
Guest
|
"Andrew Edge" <a_n_d_y_e_d_g_e@mswsystems.com> wrote in message
news:muq3t291um74hskd41c73gpmtfij5f6298@4ax.com...
Quote:
Hi.
Can anyone help me to know
what the typical Electric Power consumption is for a gas boiler having
a maximum heat output of 120000KCal/h.
Andy
The "convert" prog' makes those kCal/hour into a whopping 140kW of heat.
Which implies a small industrial unit.
About 250W for the circulating pump (if any) , solenoids and the monitor
electronics.
I'm assuming UK (cos you don't say 'furnace') so that's about 1A, so a 2Amp
fuse should be OK.
--
Posted via a free Usenet account from http://www.teranews.com |
|
|
| Back to top |
|
| Andrew Edge |
Posted: Tue Feb 13, 2007 5:13 pm |
|
|
|
Guest
|
On Tue, 13 Feb 2007 20:35:52 -0000, "john jardine"
<john@jjdesigns.fsnet.co.uk> wrote:
Quote:
"Andrew Edge" <a_n_d_y_e_d_g_e@mswsystems.com> wrote in message
news:muq3t291um74hskd41c73gpmtfij5f6298@4ax.com...
Hi.
Can anyone help me to know
what the typical Electric Power consumption is for a gas boiler having
a maximum heat output of 120000KCal/h.
Andy
The "convert" prog' makes those kCal/hour into a whopping 140kW of heat.
Which implies a small industrial unit.
About 250W for the circulating pump (if any) , solenoids and the monitor
electronics.
I'm assuming UK (cos you don't say 'furnace') so that's about 1A, so a 2Amp
fuse should be OK.
Thanks for the reply John.
We need a circuit breaker for the boiler so I'll go for one with 10
Amp and groundfault protection .As the wires are at least 1.5mm^2
they should stand that current without melting.
Andy |
|
|
| Back to top |
|
| Homer J Simpson |
Posted: Tue Feb 13, 2007 6:17 pm |
|
|
|
Guest
|
"Andrew Edge" <a_n_d_y_e_d_g_e@mswsystems.com> wrote in message
news:muq3t291um74hskd41c73gpmtfij5f6298@4ax.com...
Quote: Hi.
Can anyone help me to know
what the typical Electric Power consumption is for a gas boiler having
a maximum heat output of 120000KCal/h.
Anything from zero on up. Why does it need an electrical supply?
--
..
..
..
..
..
..
..
.. |
|
|
| Back to top |
|
| Andrew Edge |
Posted: Wed Feb 14, 2007 3:41 am |
|
|
|
Guest
|
On Tue, 13 Feb 2007 22:17:59 GMT, "Homer J Simpson"
<nobody@nowhere.com> wrote:
Quote:
"Andrew Edge" <a_n_d_y_e_d_g_e@mswsystems.com> wrote in message
news:muq3t291um74hskd41c73gpmtfij5f6298@4ax.com...
Hi.
Can anyone help me to know
what the typical Electric Power consumption is for a gas boiler having
a maximum heat output of 120000KCal/h.
Anything from zero on up. Why does it need an electrical supply?
It is for Industry. Some I can remember are Ignition, fans, Pumps,
Zone and gas valves, switchboard and programming unit, keep hot and
preheat heaters, standby power.
Andy |
|
|
| Back to top |
|
| Homer J Simpson |
Posted: Wed Feb 14, 2007 4:39 pm |
|
|
|
Guest
|
"Andrew Edge" <a_n_d_y_e_d_g_e@mswsystems.com> wrote in message
news:bre5t21utjk2u0799tc9i1l0unl1h3uis8@4ax.com...
Quote: Anything from zero on up. Why does it need an electrical supply?
It is for Industry. Some I can remember are Ignition, fans, Pumps,
Zone and gas valves, switchboard and programming unit, keep hot and
preheat heaters, standby power.
You need to add all of those up (worst case) and calculate the correct size.
--
..
..
..
..
..
..
..
.. |
|
|
| Back to top |
|
| |